EVAPCO Pass-Protect Passivation Solution
Two-step passivation system for galvanized heat exchangers that minimizes white-rust formation.
Details →
Capacitive-deionization pretreatment system that lowers makeup-water conductivity and blowdown.
EVAPCO Water Saver™ is a makeup-water pretreatment system for evaporative cooling equipment. It uses capacitive deionization to reduce dissolved-ion concentration and conductivity before the water enters a cooling tower, evaporative condenser or closed-circuit cooler.
Water passes through cylinders containing oppositely charged supercapacitors that capture dissolved ions other than silica. A typical 50% ion reduction can approximately double operating cycles of concentration without increasing scale or corrosion potential. The system achieves a 75–90% water recovery rate while reducing blowdown and treatment chemicals discharged to drain.
Capacitive-deionization pretreatment system that lowers makeup-water conductivity and blowdown.
| Equipment type | Water pretreatment system |
|---|---|
| Technology | Capacitive deionization |
| Typical ion reduction | Approximately 50% |
| Water recovery | 75–90% |
| Configurations | 9 |
| Power consumption | Below 19.2 kW |